Single Interlock
Preaction System
Bulletin 739
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Instructions for
Installation, Operation
Care and Maintenance
For Single Interlock Preaction Systems
With Dual Solenoid Actuation
Of Pneumatic Pilot Release
4"(100mm),
6"(150mm) & 165mm
Sizes with Trim
LPCB Approved
Redundant Solenoid Valve
Release
Rated to 175 psi (12.1 bar)
Externally Resetable
Clapper
One Main Drain
Bulletin 739
Vista de página 0
1 2 3 4 5 6 ... 17 18

Resumo do Conteúdo

Página 1 - Care and Maintenance

Single InterlockPreaction SystemBulletin 739The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523Instructions

Página 2 - Listing & Approvals

Technical DataReliable Single Interlock Preaction Systems, with asso-ciated trim, sizes 4” (100mm), 6” (150mm) and 165mmare rated for use at minimum w

Página 3 - Preaction systems Include:

9. Upon seeing a solid flow of water from the drain tub-ing, and the cessation of the “gurgling” sound at thedrip cup, H (Fig. 7), close valve D (Fig.

Página 4

12.Models DDX 4" (100mm), 6" (150mm) & 165mm Deluge Valve Parts ListFig. 6ItemNoPart NumberDescriptionNo.Req'd4"(100mm)Valve6&

Página 5

13.Fig. 7

Página 6 - System Operation

14.Maintenance Procedures - Model DDXDeluge ValveRefertoFigs.2,6&7.1. Mechanical sprinkler alarm (water motor–notshown) not operating:This is most

Página 7 - System Design Considerations

15.just if necessary. Clean and lubricate the twolocking pins (#17 (not shown) Fig. 6) withO-ring lubricant and drive them into the de-luge valve body

Página 8

Model LP Dry Valve Actuator Parts ListP/N 71030010Refer to Fig. 816.Note: For metric installations, a 2" NPT x R2, ISO 7/1 x Close Nipple (Reliab

Página 9

17.Fig. 9

Página 10

Installation Dimensions in Inches (mm)VALVE A B C D E F G H J K L M N P QRS4"(100mm)514(133)634(171)1314(337)778(200)2534(654)512(140)812(216)131

Página 11 - Inspection and Testing

General DescriptionReliable Single Interlock Preaction Systems are de-signed for water-sensitive areas that require protectionfrom inadvertent water f

Página 12

Fig. 13.Loss Prevention Certification Board(LPCB) Installation Requirements ofPreaction systems Include:1. Solenoid valves shall be installed in paral

Página 13

Fig. 23.

Página 14 - Deluge Valve

3.ITEMNO.PARTNUMBERDESCRIPTIONNOREQ'D16103040026MODEL DDX VALVE,ASSEMBLY, 4" (100MM)16103060024MODEL DDX VALVE,ASSEMBLY, 6" (150MM)6103

Página 15

Fig. 36.Once the clapper has opened, the lever acts as alatch, preventing the clapper from returning to theclosed position. Water from the supply flow

Página 16 - Ordering Information

7.Pressurizing Line ConnectionThe water supply for the push-rod chamber must beprovided by connection of its inlet pressurizing line to thewater suppl

Página 17

Fig. 48.

Página 18

Fig. 59.